![]() Then, the melted water conducts low-voltage electricity across the metal rings on the sensor surface. To detect moisture in dry snow or ice, the sensor’s integrated heating element must first melt the snow or ice. An automatic-start, timed-stop control system is triggered to turn on by snowfall, using moisture and temperature sensors, and turns off in a preset amount of time. The facility owner will waste far more money in energy inefficiency than is saved with this low-cost control system.Īutomatic start, timed stop. It is also easy to forget to turn this system off, which leads to unnecessary energy consumption. The lack of temperature-control sensors allows the slab to heat up too quickly, which increases the risk of stress fractures. The manual switch is used to turn a boiler and pump on and off. A simple on-off switch with no slab sensors, while economical and chosen by some, is not recommended for SIM systems. Select the right circulator and other hydronic components, such as expansion tanks.Determine the head loss through pipes, manifolds, heat source and other equipment and.Calculate the flow rate for the SIM piping system to deliver the required load.Select the type of heat transfer fluid (usually propylene glycol mixed with water).Design the piping system for delivering the calculated requirement (this includes selecting pipe size, spacing, and circuit lengths, which are typically ¾-inch PEX pipes at 9-inch spacing with circuit lengths ranging from 200 to 350 feet). ![]()